Dark mode
United Kingdom
Catalog   /   Home & Renovation   /   Autonomous Power Supply   /   UPS

Comparison Logicpower LPM-PSW-1500VA 12V 1500 VA vs Luxeon UPS-1200ZR 1200 VA

Add to comparison
Logicpower LPM-PSW-1500VA 12V 1500 VA
Luxeon UPS-1200ZR 1200 VA
Logicpower LPM-PSW-1500VA 12V 1500 VALuxeon UPS-1200ZR 1200 VA
Outdated ProductOutdated Product
TOP sellers
Typesmartsmart
Form factorstandard (flat)standard (flat)
Switching to battery6 ms5 ms
Input
Input voltage1 phase (230V)1 phase (230V)
Input voltage range145 – 280 V140-275 V
Max. current10 А
Bypass (direct connection)is absentis absent
Output
Output voltage1 phase (230V)1 phase (230V)
Peak output power1500 VA1200 VA
Rated output power1050 W850 W
Output voltage accuracy7 %
Output waveformpure sine wave (PSW)pure sine wave (PSW)
Output frequency50/60 Hz50-60 Hz
Redundant sockets22
Socket typetype F (Schuko)type F (Schuko)
Battery
Battery in set
no battery
no battery
Battery(ies) connection to UPS12 V12 V
Min. charging current10 А
Max. charging current20 А
Charging current regulation
Cold start
External battery connection
Protection
Protection
short circuit protection
overload protection
noise filtering
sound alarm
short circuit protection
overload protection
noise filtering
sound alarm
Fuseautoauto
Control interfaces
 
USB
General
Screen
Operating temperature0 – 40 °C
Dimensions (HxWxD)220x470x290 mm125x265x305 mm
Weight12.2 kg10.6 kg
Added to E-Catalogfebruary 2020june 2018

Switching to battery

The time required to transfer the load from mains power to battery power. In standby and interactive UPSs (see Type), a short-term power failure occurs at this moment — accordingly, the shorter the time to switch to the battery, the more uniform the power supply is provided by the source during a power failure. Ideally, the switching time for the traditional 50 Hz AC frequency should be less than 5 ms (a quarter of one cycle of the sine wave). With inverter UPSs, the transfer time is, by definition, zero.

Input voltage range

In this case, the input voltage range is implied, in which the UPS is able to supply a stable voltage to the load only due to its own regulators, without switching to the battery. For redundant UPSs (see "Type") this range is quite small, approximately 190 to 260 V; for interactive and especially inverter ones, it is much wider. Some UPS models allow you to manually set the input voltage range.

Max. current

The maximum current drawn by the UPS. In fact, the current reaches its maximum value only when the UPS is operating from the mains with maximum load power and a completely discharged battery. However, when calculating the load on the power grid, this parameter should be taken into account.

Peak output power

The maximum output power supplied by the UPS, in other words, the highest apparent load power allowed for this model.

This indicator is measured in volt-amperes (the general meaning of this unit is the same as that of the watt, and different names are used to separate different types of power). The total power consumption of the load, implied in this case, is the sum of two powers — active and reactive. Active power is actually effective power (it is indicated in watts in the characteristics of electrical appliances). Reactive power is the power wasted by coils and capacitors in AC devices; with numerous coils and/or capacitors, this power can be a fairly significant part of the total energy consumption. Note that for simple tasks, you can use data on effective power (it is often given for UPS — see below); but for accurate electrical calculations it is worth using the full one.

The simplest selection rule for this indicator is: the maximum output power of the UPS in volt-amperes should be at least 1.7 times higher than the total load power in watts. There are also more detailed calculation formulas that take into account the characteristics of different types of load; they can be found in special sources. As for specific values, the most modest modern UPSs give out 700 – 1000 VA, or even less — this is enough to power a PC of average performance; and in the most "heavyweight" models, th...is figure can be 8 – 10 kVA and higher.

Rated output power

The effective output power of the UPS is, in fact, the maximum active power of the load that can be connected to the device.

Active power is consumed directly for the operation of the device; it is expressed in watts. In addition to it, most AC devices also consume reactive power, which is "wasted" (relatively speaking) is spent by coils and capacitors. Apparent power (denoted in volt-amperes) is precisely the sum of active and reactive power; it is this characteristic that should be used in accurate electrical calculations. See "Maximum output power" for details; here we note that when selecting a UPS for a relatively simple application, it is quite possible to use only effective power. This is at least easier than converting the watts claimed in the characteristics of the connected devices into full power volt-amps.

The most modest modern "uninterruptibles" give out less than 500 watts. 501 – 1000 W can be considered an average value, 1.1 – 2 kW is above average, and in the most powerful models this figure exceeds 2 kW and can reach very impressive values (up to 1000 kW or more in some industrial class UPS).

Output voltage accuracy

This parameter characterizes the degree of difference between the AC voltage at the output of the UPS and the perfect voltage, the graph of which has the shape of a regular sinusoid. The perfect voltage is so named because it is the most uniform and creates the least unnecessary load on the connected devices. Thus, the distortion of the output voltage is one of the most important parameters that determine the quality of the power received by the load. A distortion level of 0% means that the UPS produces a perfect sine wave, up to 5% — slight sine wave distortion, up to 18% — strong distortion, from 18% to 40% — a trapezoidal signal, more than 40% — a square wave.

Output frequency

The frequency (frequency range) of the AC voltage output by the UPS. For computer technology, the frequency range of 47-53 Hz is considered normal, although the smaller the deviation from the 50 Hz standard, the better. On the other hand, in some UPS models, this frequency can be automatically synchronized with the frequency of the mains — so the power supplied to the load will not differ regardless of whether the load is powered by the mains or from the battery. In this case, a wider frequency range, on the contrary, is more desirable.

Min. charging current

The lowest current value in Amperes at which the UPS battery can be effectively charged. Note that charging with low currents is considered more gentle and extends the service life of the battery, but this increases the duration of the charging process. The optimal charge current is about 10% of the battery capacity.

Max. charging current

The maximum current in Amperes that charges the UPS battery or battery pack. Frequent charging cycles with high currents reduce the service life of the battery. However, charging in this mode will come in handy during regular power outages - it makes sense to use high charging currents when you need to charge the batteries as quickly as possible during the time there is light and be fully prepared for the next outages.
Logicpower LPM-PSW-1500VA 12V often compared