United Kingdom
Catalog   /   Climate, Heating, Water Heating   /   Heating & Boilers   /   Boilers

Comparison BAXI Eco-4s 24 F 24 kW vs Lemax Premium 30NV 30 kW

Add to comparison
BAXI Eco-4s 24 F 24 kW
Lemax Premium 30NV 30 kW
BAXI Eco-4s 24 F 24 kWLemax Premium 30NV 30 kW
from $493.00 up to $497.55
Outdated Product
Outdated Product
TOP sellers
Main
Light weight. Protection against disturbance of water circulation. Frost protection. Support for underfloor heating systems. Ability to work with liquefied gas.
Energy sourcegasgas
Installationwallfloor
Typedual-circuit (heating and DHW)dual-circuit (heating and DHW)
Heating area192 m²240 m²
Technical specs
Heat output24 kW30 kW
Min. heat output9.3 kW
Power supply230 Vautonomous (no electricity)
Power consumption130 W
Coolant min. T30 °С
Coolant max. T85 °С90 °С
Heating circuit max. pressure3 bar
DHW circuit max. pressure8 bar
Consumer specs
DHW min. T35 °С
DHW max. T60 °С
Performance (ΔT=25°C)13.7 L/min
Performance (ΔT ~30 °C)9.8 L/min
"Summer" mode
Heated floor mode
Circulation pump
Control busOpenTherm
Boiler specs
Efficiency92.9 %90 %
Combustion chamberclosed (turbocharged)open (atmospheric)
Flue diameter
60/100 mm /80/80 mm for separate/
130 mm
Inlet gas pressure13 mbar
Max. gas consumption2.73 m³/h1.75 m³/h
Expansion vessel capacity6 L
Expansion vessel pressure0.5 bar
Heat exchangercopper
Connections
Mains water intake1/2"2"
DHW flow1/2"2"
Gas supply3/4"1/2"
Central heating flow3/4"2"
Central heating return3/4"2"
Safety
Safety systems
gas pressure drop
water overheating
flame loss
draft control
water circulation failure
frost protection
gas pressure drop
water overheating
flame loss
draft control
 
 
More specs
Dimensions (HxWxD)730x400x299 mm961x470x556 mm
Weight30 kg85 kg
Added to E-Catalogaugust 2016december 2015

Installation

Regarding the installation method, boilers are divided into two main types: wall and floor.

Wall-mounted boilers, as the name suggests, are designed to be mounted on a wall. They usually have low power, which makes it possible to do without a separate room for their installation, and relatively small dimensions, which allow the boiler to fit into the interior of a kitchen or bathroom.

Floor boilers usually have more power than wall-mounted ones, which accordingly affects their weight, dimensions and the installation method. The weight is also due to the presence of a cast iron heat exchanger, which is considered more reliable and durable than copper, steel or silumin. Most boilers with a power of 50 kW or more and almost all boilers with a power of 100 kW or more are floor-standing.

— Parapet. They are designed for installation close to the wall; at the same time, the installation itself can be both wall-mounted and floor-mounted, depending on the dimensions and weight of the unit. All parapet boilers are gas-fired (see Energy source) and have a closed combustion chamber (see below); in this case, the flue goes directly through the wall, near which the boiler is located. One of the key advantages of such devices is their small size; a parapet boiler is considered a good option for a small city apartment or a private house with small rooms. Also, the advantages of such dev...ices are that they do not burn the air from the room and immediately remove the products of combustion to the outside. In addition, many of the boilers of this type have convection holes and during operation they also play the role of heating radiators.

Heating area

The maximum area of the building that the boiler can effectively heat. However, it is worth considering that different buildings have different thermal insulation properties and modern buildings are much “warmer” than 30-year-old and even more so 50-year-old houses. Accordingly, this paragraph is more of a reference nature and does not allow a full assessment of the actual heated area. There is a formula by which you can derive the maximum heating area, knowing the useful power of the boiler and the climatic conditions in which it will be used; see Heat output for more details. In our case, the heating area is calculated according to the formula "boiler power multiplied by 8", which is approximately equivalent to use in houses that are more than a dozen years old.

Heat output

It is the maximum useful power of the boiler.

The ability of the device to heat a room of a particular area directly depends on this parameter; by power, you can approximately determine the heating area, if this parameter is not indicated in the specs. The most general rule says that for a dwelling with a ceiling height of 2.5 – 3 m, at least 100 W of heat power is needed to heat 1 m2 of area. There are also more detailed calculation methods that take into account specific factors: the climatic zone, heat gain from the outside, design features of the heating system, etc.; they are described in detail in special sources. Also note that in dual-circuit boilers (see "Type"), part of the heat generated is used to heat water for the hot water supply; this must be taken into account when evaluating the output power.

It is believed that boilers with a power of more than 30 kW must be installed in separate rooms (boiler rooms).

Min. heat output

The minimum heat output at which the heating boiler can operate in constant mode. Operation at minimum power allows you to reduce the number of on-and-off cycles that adversely affect the durability of heating boilers.

Power supply

The type of electrical supply required for normal operation of the boiler. Power supply may be required not only for electric models but also for other types of boilers (see "Power supply") — in particular, for the operation of control automation. Connection options can be:

230 V. Work from a household system with a voltage of 230 V. At the same time, models with a power consumption of up to 3.5 kW can be connected to a standard outlet, but for high consumption devices, you need to connect directly to the distribution board. Many of the electric boilers with this connection also allow operation from 400 V (see below).

400 V. Operation from a three-phase system with a voltage of 400 V. This power supply is suitable for boilers with any power consumption. However, it is not as common as 230 V: in particular, it may be difficult to use it in a residential area. Therefore, this option is provided mainly in high-power devices for which a 230 V power supply is not suitable.

— Autonomous work. Work in completely autonomous mode, without an electricity connection. This format of operation is found in all boilers that do not use electrical heating (see "Energy source"), except for purely liquid fuel ones — in them, electricity is necessary for the operation of the fuel supply systems.

Power consumption

The maximum electrical power consumed by the boiler during operation. For non-electric models (see Energy source), this power is usually low, as it is required mainly for control circuits and it can be ignored. Regarding electric boilers, it is worth noting that the power consumption in them is most often somewhat higher than the useful one since part of the energy is inevitably dissipated and not used for heating. Accordingly, the ratio of useful and consumed power can be used to evaluate the efficiency of such a boiler.

Coolant min. T

The minimum operating temperature of the heat medium in the boiler system when operating in heating mode.

Coolant max. T

The maximum operating temperature of the heat medium in the boiler system when operating in heating mode.

Heating circuit max. pressure

The maximum pressure in the heating circuit of the boiler, at which it remains operational, and there is no risk of physical damage to the structure. For a heating system, the maximum pressure is usually about 3 bar, and for a domestic hot water circuit up to 10 bar. When the maximum pressure is exceeded, a safety valve is activated, and part of the water is discharged from the system until a normal pressure level is reached.
BAXI Eco-4s 24 F often compared