United Kingdom
Catalog   /   Climate, Heating, Water Heating   /   Heating & Boilers   /   Boilers

Comparison Ferroli DIVAproject F24 24 kW
230 V
vs Ferroli DOMIproject F24 24 kW

Add to comparison
Ferroli DIVAproject F24 24 kW 230 V
Ferroli DOMIproject F24 24 kW
Ferroli DIVAproject F24 24 kW
230 V
Ferroli DOMIproject F24 24 kW
from $411.12 up to $476.88
Outdated Product
from $432.00 up to $637.05
Outdated Product
TOP sellers
Energy sourcegasgas
Installationwallwall
Typedual-circuit (heating and DHW)dual-circuit (heating and DHW)
Heating area192 m²180 m²
Technical specs
Heat output24 kW24 kW
Power supply230 V230 V
Power consumption110 W110 W
Coolant max. T90 °С90 °С
Heating circuit max. pressure3 bar3 bar
DHW circuit max. pressure9 bar9 bar
Consumer specs
Performance (ΔT=25°C)13.4 L/min13.7 L/min
Performance (ΔT ~30 °C)11.4 L/min
"Summer" mode
Warm start
Circulation pump
Boiler specs
Efficiency91 %93 %
Combustion chamberclosed (turbocharged)closed (turbocharged)
Flue diameter
60/100 mm /80/80 mm for separate/
60/100 mm /80/80 for split flue/
Inlet gas pressure20 mbar
Max. gas consumption2.73 m³/h
Expansion vessel capacity8 L7 L
Expansion vessel pressure1 bar1 bar
Safety
Safety systems
gas pressure drop
water overheating
flame loss
draft control
 
water circulation failure
frost protection
gas pressure drop
 
flame loss
 
power outage
 
frost protection
More specs
Dimensions (HxWxD)700x400x330 mm700x400x330 mm
Weight30 kg30 kg
Added to E-Catalogaugust 2014august 2010

Heating area

A very conditional parameter that slightly characterizes the purpose based on the size of the room. And depending on the height of the ceilings, layout, building design and equipment, actual values may differ significantly. However, this item represents the maximum recommended area of the room that the boiler can effectively heat. However, it is worth considering that different buildings have different thermal insulation properties and modern buildings are much “warmer” than 30-year-old and especially 50-year-old houses. Accordingly, this item is more of a reference nature and does not allow us to fully assess the actual heated area. There is a formula by which you can derive the maximum heating area, knowing the useful power of the boiler and the climatic conditions in which it will be used; For more information on this, see "Useful Power". In our case, the heating area is calculated using the formula “boiler power multiplied by 8”, which is approximately equivalent to use in houses that are several decades old.

Performance (ΔT=25°C)

The performance of a dual-circuit boiler in the DHW supply mode when the water is heated by 25 °C above the initial temperature.

Performance is the maximum amount of hot water the unit can produce in a minute. It depends not only on the power of the heater as such, but also on how much water needs to be heated: the higher the temperature difference ΔT between cold and heated water, the more energy is required for heating and the smaller the volume of water with which the boiler can handle in this mode. Therefore, the performance of dual-circuit boilers is indicated for certain options ΔT — namely 25 °C, 30 °C and/or 50 °C. And it’s worth choosing according to this indicator, taking into account the initial water temperature and taking into account what kind of hot water demand there is at the installation site of the boiler (how many points of water intake, what are the temperature requirements, etc.). Recommendations on this subject can be found in special sources.

We also recall that water begins to be felt by a person as warm somewhere from 40 °C, as hot — somewhere from 50 °C, and the temperature of hot water in central water supply systems (according to official standards) is at least 60 °C. Thus, for the boiler to operate in the ΔT=25 °C mode and produce at least warm water at 40 °C, the initial temperature of cold water must be at least 15 °C (15+25=40 °C). It is a rather high value — for example, in a centralized water supply system, cold water...reaches 15 °C, except in summer, when the water pipes warm up noticeably; the same applies to water supplied from wells. So this performance is a very conditional value. The boiler does not work so often with a temperature difference of 25 °C. Nevertheless, the data for ΔT=25°C is still often given in the specifications — including for advertising purposes since it is in this mode that the performance figures are the highest. In addition, this information may be useful if the boiler is used as a pre-heater, and heating to operating temperature is provided by another device, such as an electric boiler or instantaneous water heater.

Performance (ΔT ~30 °C)

The performance of a dual-circuit boiler in hot water mode when water is heated by approximately 30 °C above the initial temperature.

Performance is the maximum amount of hot water the unit can produce in a minute. It depends not only on the power of the heater as such, but also on how much water needs to be heated: the higher the temperature difference ΔT between cold and heated water, the more energy is required for heating and the smaller the volume of water with which the boiler can handle in this mode. Therefore, the performance of dual-circuit boilers is indicated for certain ΔT — namely 25 °C, 30 °C and/or 50 °C. And it is worth choosing according to this indicator, taking into account the initial water temperature and taking into account what kind of hot water demand there is at the installation site of the boiler (how many points of water intake, what are the temperature requirements, etc.). Recommendations on this subject can be found in special sources.

We also recall that water begins to be felt by a person as warm somewhere from 40 °C, as hot — somewhere from 50 °C and the temperature of hot water in central water supply systems (according to official standards) is at least 60 °C. Thus, for the boiler to operate in the mode ΔT ~ 30 °C and give out at least warm water at 40 °C, the initial temperature of cold water should be about 10 °C (10 + 30=40 °C). A similar temperature can be found in wells in the warm season, and cold water in the ce...ntralized water supply system often warms up to 10 °C in the warm season. However, boilers, including dual-circuit boilers, are switched on mainly in cold weather, when the initial water temperature is noticeably lower. Accordingly, if the boiler is used as the main water heater, heating to the claimed temperatures (see "DHW min. T", "DHW max. T") often requires a greater ΔT than 30 °C, and the performance is less than indicated in this paragraph. But when operating in the preheating mode (when the water is heated to the desired temperature by an additional device like a boiler), this parameter describes the capabilities of the unit very reliably.

Efficiency

The efficiency of the boiler.

For electric models (see "Energy source"), this parameter is calculated as the ratio of net power to consumed; in such models, indicators of 98 – 99% are not uncommon. For other boilers, the efficiency is the ratio of the amount of heat directly transferred to the water to the total heat amount released during combustion. In such devices, the efficiency is lower than in electric ones; for them, a parameter of more than 90% is considered good. An exception is gas condensing boilers (see the relevant paragraph), where the efficiency can even be higher than 100%. There is no violation of the laws of physics here. It is a kind of advertising trick: when calculating the efficiency, an inaccurate method is used that does not take into account the energy spent on the formation of water vapour. Nevertheless, formally everything is correct: the boiler gives out more thermal energy to the water than is released during the combustion of fuel since condensation energy is added to the combustion energy.

Inlet gas pressure

It is the optimum gas pressure supplied to the inlet of the boiler system. Most often indicated for natural gas and is about 15-20 mbar. This parameter must match the specs of the gas supply system. However, the pressure in the latter may be higher, which may require the installation of a special gas regulator.

Max. gas consumption

Maximum gas consumption in the boiler with the corresponding energy source (see above). Achieved when the gas heater is operating at full capacity; with reduced power and consumption, respectively, will be lower.

Note that boilers of the same power may differ in gas consumption due to the difference in efficiency. While the more fuel-efficient models tend to cost more, the price difference pays off in gas savings.

Expansion vessel capacity

The capacity of the expansion tank supplied with the boiler.

The expansion tank is designed to drain excess water from the heating system when the total volume of liquid increases as a result of heating. It consists of two parts connected by a flexible membrane: in one, hermetically closed, there is air under pressure; in the other, excess water enters, compressing the membrane. In this way, a catastrophic increase in pressure in the heating circuit is avoided. The optimal volume of the expansion tank depends on several system parameters, primarily the volume and composition of the coolant; detailed recommendations for calculations can be found in special sources.

Safety systems

Gas pressure drop. This protection system ensures that the boiler is switched off in the event of a critical drop in gas pressure, insufficient for the normal functioning of the burner. In the event of such a fall, the valve that supplies gas to the burner is closed and blocked. After the restoration of gas pressure, it also remains closed; it is necessary to open it and resume the gas supply manually.

Water overheating. A temperature sensor automatically turns off the boiler when the temperature of the water in the system is critically exceeded.

Flame loss. Flame loss protection is based on a sensor that monitors the combustion of gas and automatically stops its supply. It prevents the room from filling with gas and the possible tragic consequences of this.

Draft control. In boilers with an open combustion chamber, to maintain normal conditions in the room where such a boiler is installed, constant removal of products of combustion into the atmosphere is necessary. The lack of a normal draft in the chimney can lead to the accumulation of combustion products in the room. The draft protection system prevents this by automatically turning off the boiler when it detects the release of combustion products outside the chimney.

Power outage. Most modern boilers h...ave an electronic control system; in addition, many structural elements (pumps, valves, fans, etc.) are also powered by electricity. Thus, a power outage during the operation of the boiler will inevitably lead to an abnormal mode of operation, which is fraught with breakdowns and even accidents. To prevent such cases, a power outage protection system is installed, which completely stops the operation of the boiler in the event of a power outage. When the power supply is restored, the boiler needs to be restarted manually.

Water circulation failure. This protection system controls the normal movement of the water through the heating circuit. Water circulation failure can lead to overheating of some elements of the boiler and damage to it. To avoid this, if the circulation is disturbed, the system turns off the pump and shuts off the gas supply to the burner.

Frost protection. A system that controls the temperature in the heating circuit. Freezing of the liquid in the circuit disrupts the normal operation of the heating, which may require heating of the pipes and lead to system damage. To avoid this, when the water temperature drops below 5 °C, the burner is ignited, the circulation pump is activated, and the circuit warms up to a temperature of about 35 °C — thus preventing the formation of ice in the pipes.
Ferroli DIVAproject F24 often compared
Ferroli DOMIproject F24 often compared