Dark mode
United Kingdom
Catalog   /   Climate, Heating, Water Heating   /   Heating & Boilers   /   Circulation Pumps

Comparison Grundfos UPA 15-120 12 m
3/4"
vs Sprut GPD 15-12A 13 m
195 mm

Add to comparison
Grundfos UPA 15-120 12 m 3/4"
Sprut GPD 15-12A 13 m 195 mm
Grundfos UPA 15-120 12 m
3/4"
Sprut GPD 15-12A 13 m
195 mm
Outdated Product
from $107.04 up to $135.16
Outdated Product
TOP sellers
Main functioncold water pressure boostcold water pressure boost
Designsingle headsingle head
Pump typecentrifugalcentrifugal
Rotor typewetwet
Specs
Max. flow2400 L/h3500 L/h
Max. head12 m13 m
Minimum operating pressure0.2 bar
Max. operating pressure10 bar6 bar
Minimum fluid temperature2 °С
Max. fluid temperature60 °С40 °С
Features
1 speed
automatic operating mode
stepless adjustment
automatic operating mode
Motor
Max. power consumption200 W270 W
Mains voltage230 V230 V
Motor typeasynchronous
Shaft arrangementhorizontalhorizontal
Shaft materialcermet
Connection
Connection typethreadthread
Inlet/outlet arrangementcoaxiallycoaxially
Inlet3/4"3/4"
Outlet3/4"3/4"
More specs
Pump housing materialcast ironcast iron
Impeller materialplastic
Country of brand originDenmarkUkraine
Protection classIP42IP44
Insulation classH
Port-to-port length195 mm
Dimensions (HxWxD)150x132x195 mm
Weight4.5 kg
Added to E-Catalogapril 2019november 2014

Max. flow

The maximum flow of a pump is the amount of liquid it can pump in a certain amount of time.

Features of choosing the optimal performance option depend primarily on the purpose of the pump (see above). For example, for DHW recirculation models, the pump performance should not exceed the performance of the water heater. If the water heater is capable of delivering 10 litres per minute to the DHW circuit, then the maximum pump performance will be 10*60=600 L/h. The basic formula for calculating the performance of a heating system takes into account the power of the heater and the temperature difference at the inlet and outlet, and for the cold water system — the number of points of water intake. More detailed information about the calculations for each application can be found in special sources, and it is better to entrust the calculations themselves to professionals.

Max. head

The head can be described as the maximum height to which a pump can lift liquid through a vertical pipe without bending or branching. This parameter is directly related to the pressure that the pump produces: 10 m of head approximately corresponds to a pressure of 1 bar (do not confuse this parameter with operating pressure — see more about it below).

The head is one of the key specs for most circulation pumps. Traditionally, it is calculated based on the difference in height between the location of the pump and the highest point of the system; however, this principle is relevant only for units that boost the pressure of cold water(see "Suitable for"). Circulation pumps for heating and DHW work with closed circuits, and the optimal pressure depends on the total hydraulic resistance of the system. Detailed calculation formulas for the first and second cases can be found in special sources.

Minimum operating pressure

The lowest pressure in the circuit where the pump is connected, at which it can perform the main task (see "Suitable for"), providing the claimed operating parameters. The technical features of many modern models are such that some of them can operate at almost zero pressure, simply by the presence of water in the pipe; therefore, this parameter may not be specified at all.

Max. operating pressure

The highest pressure in the circuit at which the pump will be able to work normally.

Of course, this parameter cannot be exceeded — the unit may fail due to a breakdown caused by too high pressure (and even if this did not happen right away, it can happen at any time). However, it is worth choosing a model with some margin — so that the pump can normally withstand pressure surges, which are almost inevitable in any pipe.

Minimum fluid temperature

The lowest fluid temperature at which the pump is capable of operating normally.

Almost all pumps can normally transfer cool water, regardless of the purpose (see above); therefore, for normal household use, this parameter is not critical and for some models, it may not be indicated at all. But if you need the ability to work with liquids with temperatures below 15 °C, you should pay close attention to the minimum temperature. Some models that can be used with antifreeze normally tolerate even temperatures below zero.

Max. fluid temperature

The highest liquid temperature that the pump is capable of operating normally.

The possibility of using the unit directly depends on this parameter (see "Suitable for"): for example, models for heating systems must tolerate a temperature of at least 95 °C, and for DHW supply — at least 65 °C. Well, anyway, this parameter should not be exceeded: an overheated pump will fail very quickly, and the consequences of this can be very unpleasant.

Features

— Number of speeds. The number of speeds provided in the design of the pump. Each speed corresponds to its performance value (see above). The options could be:
  • 1 speed. There are no adjustments in such models; when turned on, the pump can operate only at one speed. This is the simplest and most inexpensive option, due to the absence of additional elements (regulators) in the design. Of course, it is convenient only in cases where the unit must operate at full capacity every time it is turned on.
  • 2 speeds. 2 speeds give the user some degree of choice: the pump does not have to be turned on at full power — when it is not required, the unit can be run at reduced power to save electricity and not wear out the mechanisms beyond what is necessary.
  • 3 speeds. The largest number of adjustments found in modern pumps — it makes no sense to provide a larger number for many reasons. It gives even more options for setting operation parameters than 2 speeds.
  • Stepless adjustment. This option implies the ability to set the regulator to any position from minimum to maximum (in some models, fixed settings may also be provided, but only as an additional option). It provides maximum freedom and precision in the choice of operating mode. However, it significantly affects the price; and the real need for smooth adjustment occurs quite rarely.
Automatic operating mode.... The essence of this function differs depending on the purpose of the device (see above). So, in models for increasing the pressure of cold water, the automation turns on the pump when the tap is opened and turns it off when it is closed — a special sensor reacts to the movement of water. In models for heating and domestic hot water, automation is responsible for adjusting the operating parameters — for example, when screwing the valves and reducing the flow rate, the pump can reduce the pressure, as well as, for additional functions, such as an on-off timer. Anyway, this feature makes life easier for the user, eliminating the need to perform certain operations manually and adding new features to the pump; but the specific set of these features depends on the model.

Display. Various additional information can be displayed on the display: operating mode, performance settings, water temperature, set timers, error messages and much more. It makes management more convenient and intuitive. Pumps usually use the simplest form of black and white LCD screens, but this is quite sufficient for the purposes mentioned.

Control panel. In this case, the control panel means a panel that has a switch with a choice of operating modes between automatic (see above) and manual. Accordingly, the presence of several modes almost necessarily means the presence of a control panel. But the speed switches themselves are not considered for this function.

Max. power consumption

The electrical power consumed by the pump during normal operation and maximum performance.

This indicator directly depends on performance — after all, for pumping large volumes of water, an appropriate amount of energy is needed. And the power depends on two main parameters — electricity consumption and the load on the power grid, which determines the connection rules. For example, pumps with a power of more than 5 kW cannot be connected to ordinary household sockets; more detailed rules can be found in special sources.

Motor type

The type of electric motor provided in the design of the pump.

— Asynchronous. Engines of this type have the simplicity of design and low price, combined with reliability. Their main disadvantage is the dependence of the rotational speed on the load, which leads to the fact that it is difficult to adjust this frequency accurately for such an engine. At the same time, for domestic use, it is not critical and in the professional sphere, it rarely creates difficulties. Therefore, induction motors are very popular in modern pumps.

— Synchronous. Synchronous motors are distinguished by high accuracy in speed control — it practically does not depend on the load on the rotor; this is their main advantage over asynchronous ones. On the other hand, this type is more complex and expensive, and the need for fine adjustment is quite rare. Therefore, synchronous electric motors are mainly installed in high-end pumps designed for use in specific conditions.
Grundfos UPA 15-120 often compared
Sprut GPD 15-12A often compared